2400VOLT POWER CABLE
SINGLE CONDUCTOR NONSHIELDED EPR/PVC
TYPE MV-90 WET OR DRY
| Construction: |
| CONDUCTOR: |
CLASS B STRANDED ANNEALED BARE COPPER.
|
| INSULATION: |
ETHYLENE PROPYLENE RUBBER (EPR).
|
| STRAND SHIELD: |
EXTRUDED NONMETALLIC SEMI-CONDUCTING LAYER.
|
| JACKET: |
SUNLIGHT AND MOISTURE RESISTANT PVC (POLYVINYL CHLORIDE).
|
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Strands |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. |
Ampacity in *Conduit |
Add to Quote Cart |
| CW07021 |
8 |
7 |
0.125 |
0.08 |
.59" |
197 |
55 |
|
| CW07022 |
6 |
7 |
0.125 |
0.08 |
.64" |
262 |
75 |
|
| CW07023 |
4 |
7 |
0.125 |
0.08 |
.69" |
332 |
97 |
|
| CW07024 |
2 |
7 |
0.125 |
0.08 |
.76" |
438 |
130 |
|
| CW07025 |
1 |
19 |
0.125 |
0.08 |
.81" |
510 |
155 |
|
| CW07026 |
1/0 |
19 |
0.125 |
0.08 |
.84" |
595 |
180 |
|
| CW07027 |
2/0 |
19 |
0.125 |
0.08 |
.88" |
705 |
205 |
|
| CW07028 |
3/0 |
19 |
0.125 |
0.08 |
.97" |
870 |
240 |
|
| CW07029 |
4/0 |
19 |
0.125 |
0.08 |
1.02" |
1023 |
280 |
|
| CW07030 |
250MCM |
37 |
0.14 |
0.11 |
1.13" |
1215 |
315 |
|
| CW07031 |
350MCM |
37 |
0.14 |
0.11 |
1.25" |
1550 |
385 |
|
| CW07032 |
500MCM |
37 |
0.14 |
0.11 |
1.38" |
2132 |
475 |
|
| CW07033 |
750MCM |
61 |
0.155 |
0.125 |
1.63" |
3100 |
600 |
|
| CW07034 |
1000MCM |
61 |
0.155 |
0.125 |
1.78" |
3980 |
690 |
|
| Displaying 1 to 14 (of 14 products) |
Result Pages: 1 |
| * Ampacity based on 3 cables in isolated conduit in air, 90°C temperature, 40°C ambient per NEC 310-73.
|
| Application |
| Suitable for use as a 2400Volt nonshielded power cable in wet or dry locations at conductor temperatures not exceeding 90°C.
|
| Where NEC is not required, cable is also suitable for use in
|
| 1) metal or nonmetallic conduit in wet or dry locations in conduits up to 4160Volts,
|
| 2) single conductor or triplexed singles in aerial installation with grounded messenger,
|
| 3) single conductor (mounted on insulators) in indoor/outdoor locations in free air, and
|
| 4) single conductor or triplexed singles in cable tray in circuits up to 4160 Volts.
|
| Standards |
| UL 1072 for Medium Voltage Cables.
|
| ICEA S-96-659/NEMA WC71 for Nonshielded 2001 - 5KV Cables. (Formerly ICEA S-68-516/NEMA WC-8).
|
| NEC Articles 310 and 328 for MV-90 Cable Uses and Constructions.
|
|
|