2400VOLT POWER CABLE
SINGLE CONDUCTOR NONSHIELDED EPR/PVC
TYPE MV-90 WET OR DRY

Construction:
CONDUCTOR: CLASS B STRANDED ANNEALED BARE COPPER.
INSULATION: ETHYLENE PROPYLENE RUBBER (EPR).
STRAND SHIELD: EXTRUDED NONMETALLIC SEMI-CONDUCTING LAYER.
JACKET: SUNLIGHT AND MOISTURE RESISTANT PVC (POLYVINYL CHLORIDE).
 Charlotte Wire Part# ↓   Size AWG   Number of Strands   Insulation Thickness (in.)   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt.   Ampacity in *Conduit   Add to Quote Cart 
CW07021 8 7 0.125 0.08 .59" 197 55 Request Quote For This Product 
CW07022 6 7 0.125 0.08 .64" 262 75 Request Quote For This Product 
CW07023 4 7 0.125 0.08 .69" 332 97 Request Quote For This Product 
CW07024 2 7 0.125 0.08 .76" 438 130 Request Quote For This Product 
CW07025 1 19 0.125 0.08 .81" 510 155 Request Quote For This Product 
CW07026 1/0 19 0.125 0.08 .84" 595 180 Request Quote For This Product 
CW07027 2/0 19 0.125 0.08 .88" 705 205 Request Quote For This Product 
CW07028 3/0 19 0.125 0.08 .97" 870 240 Request Quote For This Product 
CW07029 4/0 19 0.125 0.08 1.02" 1023 280 Request Quote For This Product 
CW07030 250MCM 37 0.14 0.11 1.13" 1215 315 Request Quote For This Product 
CW07031 350MCM 37 0.14 0.11 1.25" 1550 385 Request Quote For This Product 
CW07032 500MCM 37 0.14 0.11 1.38" 2132 475 Request Quote For This Product 
CW07033 750MCM 61 0.155 0.125 1.63" 3100 600 Request Quote For This Product 
CW07034 1000MCM 61 0.155 0.125 1.78" 3980 690 Request Quote For This Product 
Displaying 1 to 14 (of 14 products) Result Pages:  1 
* Ampacity based on 3 cables in isolated conduit in air, 90°C temperature, 40°C ambient per NEC 310-73.
Application
Suitable for use as a 2400Volt nonshielded power cable in wet or dry locations at conductor temperatures not exceeding 90°C.
Where NEC is not required, cable is also suitable for use in
1) metal or nonmetallic conduit in wet or dry locations in conduits up to 4160Volts,
2) single conductor or triplexed singles in aerial installation with grounded messenger,
3) single conductor (mounted on insulators) in indoor/outdoor locations in free air, and
4) single conductor or triplexed singles in cable tray in circuits up to 4160 Volts.
Standards
UL 1072 for Medium Voltage Cables.
ICEA S-96-659/NEMA WC71 for Nonshielded 2001 - 5KV Cables. (Formerly ICEA S-68-516/NEMA WC-8).
NEC Articles 310 and 328 for MV-90 Cable Uses and Constructions.