2400VOLT POWER CABLE
SINGLE CONDUCTOR NONSHIELDED EPR/HYPALON®
TYPE MV-90 WET OR DRY

Construction:
CONDUCTOR: CLASS B STRANDED ANNEALED BARE COPPER.
INSULATION: ETHYLENE PROPYLENE RUBBER (EPR).
STRAND SHIELD: EXTRUDED NONMETALLIC SEMI-CONDUCTING LAYER.
JACKET: FLAME AND MOISTURE RESISTANT BLACK HYPALON®. (CHLOROSULFONATED POLYETHYLENE)
 Charlotte Wire Part# ↑   Size AWG   Number of Strands   Insulation Thickness (in.)   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt.   Ampacity in **Conduit   Add to Quote Cart 
CW07054 1000MCM 61 0.155 0.125 1.78" 3980 690 Request Quote For This Product 
CW07053 750MCM 61 0.155 0.125 1.63" 3100 600 Request Quote For This Product 
CW07052 500MCM 37 0.14 0.11 1.38" 2132 475 Request Quote For This Product 
CW07051 350MCM 37 0.14 0.11 1.25" 1550 385 Request Quote For This Product 
CW07050 250MCM 37 0.14 0.11 1.13" 1215 315 Request Quote For This Product 
CW07049 4/0 19 0.125 0.08 1.02" 1023 280 Request Quote For This Product 
CW07048 3/0 19 0.125 0.08 .97" 870 240 Request Quote For This Product 
CW07047 2/0 19 0.125 0.08 .88" 705 205 Request Quote For This Product 
CW07046 1/0 19 0.125 0.08 .84" 595 180 Request Quote For This Product 
CW07045 1 19 0.125 0.08 .81" 510 155 Request Quote For This Product 
CW07044 2 7 0.125 0.08 .76" 438 130 Request Quote For This Product 
CW07043 4 7 0.125 0.08 .69" 332 97 Request Quote For This Product 
CW07042 6 7 0.125 0.08 .64" 262 75 Request Quote For This Product 
CW07041 8 7 0.125 0.08 .59" 197 55 Request Quote For This Product 
Displaying 1 to 14 (of 14 products) Result Pages:  1 
® Hypalon® is a Dupont Trademark. (Also known as chlorosulfonated polyethylene or CSPE.)
** Ampacity based on 3 cables in isolated conduit in air, 90°C temperature, 40°C ambient per NEC 310-73.
Application
Suitable for use as a 2400Volt nonshielded power cable in wet or dry locations at conductor temperatures not exceeding 90°C.
Also listed for Cable Tray Use in sizes 1/0 AWG and larger.
Where NEC is not required, cable is also suitable for use in
1) metal or nonmetallic conduit in wet or dry locations in conduits up to 4160Volts,
2) single conductor or triplexed singles in aerial installation with grounded messenger,
3) single conductor (mounted on insulators) in indoor/outdoor locations in free air, and
4) single conductor or triplexed singles in cable tray in circuits up to 4160Volts.
Standards
UL 1072 for Medium Voltage Cables.
ICEA S-96-659/NEMA WC71 for Nonshielded 2001 - 5KV Cables. (Formerly ICEA S-68-516/NEMA WC-8).
Passes UL&IEEE 70,000BTU Flame Test (1/0 and larger).
NEC Article 392 for CT Use (Sizes 1/0 and larger).
NEC Articles 310 and 328 for MV-90 Cable uses and constructions.