5KV POWER CABLE
SINGLE CONDUCTOR SHIELDED EPR/PVC JACKET
TYPE MV-105 5KV 133% OR 8KV 100% INSULATION LEVEL

Construction:
CONDUCTOR: CLASS B STRANDED ANNEALED BARE COPPER.
INSULATION: ETHYLENE PROPYLENE RUBBER (EPR).
STRAND SHIELD: NONMETALLIC SEMI-CONDUCTING EXTRUDED LAYER.
INSULATION SHIELDING: NONMETALLIC LAYER: SEMI-CONDUCTING EXTRUSION DIRECTLY OVER INSULATION.
METALLIC LAYER: LAPPED COPPER TAPE SHIELD DIRECTLY OVER NONMETALLIC LAYER.
OVERALL JACKET: SUNLIGHT RESISTANT, BLACK POLYVINYL CHLORIDE (PVC).
 Charlotte Wire Part# ↓   Size AWG   Number of Strands   Insulation Thickness (in.)   Insulation Diameter (in.)   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt.   Ampacity in *Conduit   Add to Quote Cart 
CW07102 6 7 0.115 .45" 0.06 .68" 290 84 Request Quote For This Product 
CW07103 4 7 0.115 .51" 0.06 .73" 360 110 Request Quote For This Product 
CW07104 2 7 0.115 .57" 0.06 .78" 465 145 Request Quote For This Product 
CW07105 1 19 0.115 .61" 0.06 .82" 560 175 Request Quote For This Product 
CW07106 1/0 19 0.115 .65" 0.08 .90" 650 200 Request Quote For This Product 
CW07107 2/0 19 0.115 .69" 0.08 .96" 758 225 Request Quote For This Product 
CW07108 3/0 19 0.115 .74" 0.08 1.02" 910 270 Request Quote For This Product 
CW07109 4/0 19 0.115 .80" 0.08 1.05" 1060 305 Request Quote For This Product 
CW07110 250MCM 37 0.115 .85" 0.08 1.11" 1220 355 Request Quote For This Product 
CW07111 350MCM 37 0.115 .95" 0.08 1.22" 1580 430 Request Quote For This Product 
CW07112 500MCM 37 0.115 1.08" 0.08 1.35" 2120 530 Request Quote For This Product 
CW07113 750MCM 61 0.115 1.28" 0.08 1.54" 3101 665 Request Quote For This Product 
CW07114 1000MCM 61 0.115 1.41" 0.08 1.80" 3890 770 Request Quote For This Product 
Displaying 1 to 13 (of 13 products) Result Pages:  1 
* Ampacity based on 3 cables at 5kv in isolated conduit in air, 105°C temperature, 40°C ambient per NEC 310-73.
Application
Suitable as a power cable for circuits up to 5000Volts at 133%(ungrounded) insulation level or up to 8000Volts at 100% (grounded) insulation level in wet or dry locations at conductor temperatures not exceeding 105°C.
Suitable installations include conduit, trough, open tray, duct, aerial, and direct burial.
Standards
UL 1072 for Medium Voltage Cables.
ICEA S-93-639/NEMA WC74 for Shielded Power Cables. (Formerly ICEA S-68-516/NEMA WC8)
AEIC CS-6 For EPR Insulated Shielded Power Cables.
NEC Article 310 & 328 for MV-105 Cable Uses and Constructions.
Optional Constructions
CT Use rating (1/0AWG and larger).
Hypalon® or CPE outer jacket.
Insulation thickness of 90mils.
MV-90 rating.