5KV POWER CABLE
SINGLE CONDUCTOR SHIELDED EPR/PVC JACKET
TYPE MV-105 5KV 133% OR 8KV 100% INSULATION LEVEL
| Construction: |
| CONDUCTOR: |
CLASS B STRANDED ANNEALED BARE COPPER.
|
| INSULATION: |
ETHYLENE PROPYLENE RUBBER (EPR).
|
| STRAND SHIELD: |
NONMETALLIC SEMI-CONDUCTING EXTRUDED LAYER.
|
| INSULATION SHIELDING: |
NONMETALLIC LAYER: SEMI-CONDUCTING EXTRUSION DIRECTLY OVER INSULATION.
|
| METALLIC LAYER: |
LAPPED COPPER TAPE SHIELD DIRECTLY OVER NONMETALLIC LAYER.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, BLACK POLYVINYL CHLORIDE (PVC).
|
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Strands |
Insulation Thickness (in.) |
Insulation Diameter (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. |
Ampacity in *Conduit |
Add to Quote Cart |
| CW07102 |
6 |
7 |
0.115 |
.45" |
0.06 |
.68" |
290 |
84 |
|
| CW07103 |
4 |
7 |
0.115 |
.51" |
0.06 |
.73" |
360 |
110 |
|
| CW07104 |
2 |
7 |
0.115 |
.57" |
0.06 |
.78" |
465 |
145 |
|
| CW07105 |
1 |
19 |
0.115 |
.61" |
0.06 |
.82" |
560 |
175 |
|
| CW07106 |
1/0 |
19 |
0.115 |
.65" |
0.08 |
.90" |
650 |
200 |
|
| CW07107 |
2/0 |
19 |
0.115 |
.69" |
0.08 |
.96" |
758 |
225 |
|
| CW07108 |
3/0 |
19 |
0.115 |
.74" |
0.08 |
1.02" |
910 |
270 |
|
| CW07109 |
4/0 |
19 |
0.115 |
.80" |
0.08 |
1.05" |
1060 |
305 |
|
| CW07110 |
250MCM |
37 |
0.115 |
.85" |
0.08 |
1.11" |
1220 |
355 |
|
| CW07111 |
350MCM |
37 |
0.115 |
.95" |
0.08 |
1.22" |
1580 |
430 |
|
| CW07112 |
500MCM |
37 |
0.115 |
1.08" |
0.08 |
1.35" |
2120 |
530 |
|
| CW07113 |
750MCM |
61 |
0.115 |
1.28" |
0.08 |
1.54" |
3101 |
665 |
|
| CW07114 |
1000MCM |
61 |
0.115 |
1.41" |
0.08 |
1.80" |
3890 |
770 |
|
| Displaying 1 to 13 (of 13 products) |
Result Pages: 1 |
| * Ampacity based on 3 cables at 5kv in isolated conduit in air, 105°C temperature, 40°C ambient per NEC 310-73.
|
| Application |
| Suitable as a power cable for circuits up to 5000Volts at 133%(ungrounded) insulation level or up to 8000Volts at 100% (grounded) insulation level in wet or dry locations at conductor temperatures not exceeding 105°C.
|
| Suitable installations include conduit, trough, open tray, duct, aerial, and direct burial.
|
| Standards |
| UL 1072 for Medium Voltage Cables.
|
| ICEA S-93-639/NEMA WC74 for Shielded Power Cables. (Formerly ICEA S-68-516/NEMA WC8)
|
| AEIC CS-6 For EPR Insulated Shielded Power Cables.
|
| NEC Article 310 & 328 for MV-105 Cable Uses and Constructions.
|
| Optional Constructions |
| CT Use rating (1/0AWG and larger).
|
| Hypalon® or CPE outer jacket.
|
| Insulation thickness of 90mils.
|
| MV-90 rating.
|
|
|