5KV POWER CABLE
THREE CONDUCTOR W/GND SHIELDED EPR O/A PVC JACKET
TYPE MV-105 5KV 133% OR 8KV 100% INSULATION LEVEL
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
CLASS B STRANDED ANNEALED BARE COPPER.
|
| INSULATION: |
ETHYLENE PROPYLENE RUBBER (EPR).
|
| CABLE ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND WIRE IN ONE OF THE INTERSTICES, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE.
|
| STRAND SHIELD: |
NONMETALLIC SEMI-CONDUCTING EXTRUDED LAYER.
|
| INSULATION SHIELDING: |
NONMETALLIC LAYER: SEMI-CONDUCTING EXTRUSION DIRECTLY OVER INSULATION.
|
| METALLIC LAYER: |
LAPPED COPPER TAPE SHIELD DIRECTLY OVER NONMETALLIC LAYER.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, BLACK POLYVINYL CHLORIDE (PVC).
|
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Strands |
Insulation Thickness (in.) |
Ground Wire Size |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. |
Ampacity in *Duct |
Add to Quote Cart |
| CW07130 |
6 |
7 |
0.115 |
6 |
0.08 |
1.37" |
820 |
84 |
|
| CW07131 |
4 |
7 |
0.115 |
6 |
0.08 |
1.48" |
1320 |
110 |
|
| CW07132 |
2 |
7 |
0.115 |
6 |
0.08 |
1.56" |
1590 |
145 |
|
| CW07133 |
1 |
19 |
0.115 |
4 |
0.08 |
1.65" |
1850 |
165 |
|
| CW07134 |
1/0 |
19 |
0.115 |
4 |
0.11 |
1.78" |
2190 |
190 |
|
| CW07135 |
2/0 |
19 |
0.115 |
4 |
0.11 |
1.88" |
2580 |
220 |
|
| CW07136 |
3/0 |
19 |
0.115 |
3 |
0.11 |
1.99" |
3050 |
250 |
|
| CW07137 |
4/0 |
19 |
0.115 |
3 |
0.11 |
2.12" |
3600 |
285 |
|
| CW07138 |
250MCM |
37 |
0.115 |
3 |
0.11 |
2.26" |
4100 |
315 |
|
| CW07139 |
350MCM |
37 |
0.115 |
2 |
0.11 |
2.48" |
5380 |
380 |
|
| CW07140 |
500MCM |
37 |
0.115 |
1 |
0.11 |
2.80" |
7250 |
460 |
|
| CW07141 |
750MCM |
61 |
0.115 |
1/0 |
0.11 |
3.25" |
10300 |
570 |
|
| CW07142 |
1000MCM |
61 |
0.115 |
1/0 |
0.11 |
3.60" |
13040 |
645 |
|
| Displaying 1 to 13 (of 13 products) |
Result Pages: 1 |
| * Ampacities are based on 2002 NEC table 310.79, three conductors within overall covering in one underground duct, 105°C conductor temperature, 20°C earth ambient temperature.
|
| Application |
| Suitable as a power cable for circuits up to 5000Volts at 133%(ungrounded) insulation level or up to 8000Volts at 100% (grounded) insulation level in wet or dry locations at conductor temperatures not exceeding 105°C.
|
| Suitable installations include conduit, trough, open tray, duct, aerial, and direct burial.
|
| Standards |
| UL 1072 for Medium Voltage Cables.
|
| ICEA S-93-639/NEMA WC74 for Shielded Power Cables. (Formerly ICEA S-68-516/NEMA WC8)
|
| AEIC CS-6 for EPR Insulated Shielded Power Cables.
|
| NEC Article 310 & 328 for MV-105 Cable Uses and Constructions.
|
| NEC Article 392 for Cable Tray use.
|
| Optional Constructions |
| PVC jackets on singles.
|
| Hypalon® or CPE outer jacket.
|
|
|
|