15KV POWER CABLE
SINGLE CONDUCTOR SHIELDED EPR/PVC JACKET
TYPE MV-105 133% INSULATION LEVEL
| Construction: |
| CONDUCTOR: |
CLASS B STRANDED ANNEALED BARE COPPER.
|
| INSULATION: |
ETHYLENE PROPYLENE RUBBER (EPR).
|
| STRAND SHIELD: |
NONMETALLIC SEMI-CONDUCTING EXTRUDED LAYER.
|
| INSULATION SHIELDING: |
|
| NONMETALLIC LAYER: |
SEMI-CONDUCTING EXTRUSION DIRECTLY OVER INSULATION.
|
| METALLIC LAYER: |
LAPPED COPPER TAPE SHIELD DIRECTLY OVER NONMETALLIC LAYER.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, BLACK POLYVINYL CHLORIDE (PVC).
|
| Charlotte Wire Part# ↑ |
Size AWG |
Number of Strands |
Insulation Thickness (in.) |
Insulation Diameter (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Ampacity in *Conduit |
Add to Quote Cart |
| CW07261 |
1000MCM |
61 |
0.22" |
1.65" |
0.11" |
2.00" |
4410 |
755 |
|
| CW07260 |
750MCM |
61 |
0.22" |
1.48" |
0.11" |
1.84" |
3420 |
655 |
|
| CW07259 |
500MCM |
37 |
0.22" |
1.30" |
0.08" |
1.59" |
2400 |
535 |
|
| CW07258 |
350MCM |
37 |
0.22" |
1.18" |
0.08" |
1.45" |
1880 |
440 |
|
| CW07257 |
250MCM |
37 |
0.22" |
1.08" |
0.08" |
1.35" |
1470 |
365 |
|
| CW07256 |
4/0 |
19 |
0.22" |
1.01" |
0.08" |
1.28" |
1290 |
330 |
|
| CW07255 |
3/0 |
19 |
0.22" |
0.96" |
0.08" |
1.22" |
1130 |
290 |
|
| CW07254 |
2/0 |
19 |
0.22" |
0.90" |
0.08" |
1.15" |
980 |
255 |
|
| CW07253 |
1/0 |
19 |
0.22" |
0.86" |
0.08" |
1.13" |
850 |
215 |
|
| CW07252 |
1 |
19 |
0.22" |
0.82" |
0.08" |
1.09" |
770 |
190 |
|
| CW07251 |
2 |
7 |
0.22" |
0.78" |
0.08 |
1.04" |
690 |
165 |
|
| Displaying 1 to 11 (of 11 products) |
Result Pages: 1 |
| * Ampacity based on 3 cables in isolated conduit in air, 105°C temperature, 40°C ambient per NEC 310-73.
|
| Application |
| Suitable as a power cable for circuits up to 15000Volts at 133% (ungrounded) insulation level in wet or dry locations at conductor temperatures not exceeding 105°C.
|
| Suitable installations include conduit, trough, open tray, duct, aerial, and direct burial.
|
| Standards |
| UL 1072 for Medium Voltage Cables.
|
| ICEA S-93-639/NEMA WC74 for Shielded Power Cables. (Formerly ICEA S-68-516/NEMA WC8).
|
| AEIC CS-8 for EPR Shielded Cables.
|
| NEC Article 310 & 328 for MV-105 Cable uses and constructions.
|
| Optional Constructions |
| CT Use rating (1/0AWG and larger).
|
| Hypalon® or CPE outer jacket.
|
| MV-90 rating.
|
|
|