15KV POWER CABLE
THREE CONDUCTOR W/GND SHIELDED EPR O/A PVC JACKET
TYPE MV-105 15KV 133% INSULATION LEVEL
| Construction: |
| CONDUCTOR: |
CLASS B STRANDED ANNEALED BARE COPPER.
|
| STRAND SHIELD: |
NONMETALLIC SEMI-CONDUCTING EXTRUDED LAYER.
|
| INSULATION: |
ETHYLENE PROPYLENE RUBBER (EPR).
|
| INSULATION SHIELDING:
|
| NONMETALLIC LAYER: |
SEMI-CONDUCTING EXTRUSION DIRECTLY OVER INSULATION.
|
| METALLIC LAYER: |
LAPPED COPPER TAPE SHIELD DIRECTLY OVER NONMETALLIC LAYER.
|
| CABLE ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND WIRE IN ONE OF THE INTERSTICES, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, BLACK POLYVINYL CHLORIDE (PVC).
|
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Strands |
Insulation Thickness (in.) |
Ground Wire Size |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. |
Ampacity in *Duct |
Add to Quote Cart |
| CW07281 |
2 |
7 |
.220" |
6 |
.110" |
2.11" |
2290 |
160 |
|
| CW07282 |
1 |
19 |
.220" |
4 |
.110" |
2.15" |
2580 |
185 |
|
| CW07283 |
1/0 |
19 |
.220" |
4 |
.110" |
2.25" |
2920 |
210 |
|
| CW07284 |
2/0 |
19 |
.220" |
4 |
.110" |
2.34" |
3270 |
235 |
|
| CW07285 |
3/0 |
19 |
.220" |
3 |
.110" |
2.45" |
3760 |
270 |
|
| CW07286 |
4/0 |
19 |
.220" |
3 |
.110" |
2.58" |
4300 |
305 |
|
| CW07287 |
250MCM |
37 |
.220" |
3 |
.110" |
2.70" |
4940 |
335 |
|
| CW07288 |
350MCM |
37 |
.220" |
2 |
.140" |
2.98" |
6280 |
400 |
|
| CW07289 |
500MCM |
37 |
.220" |
1 |
.140" |
3.25" |
8110 |
485 |
|
| CW07290 |
750MCM |
61 |
.220" |
1/0 |
.140" |
3.68" |
11160 |
585 |
|
| CW07291 |
1000MCM |
61 |
.220" |
1/0 |
.140" |
3.96" |
14280 |
660 |
|
| Displaying 1 to 11 (of 11 products) |
Result Pages: 1 |
| * Ampacities are based on 2005 NEC table 310.79, three conductors within overall covering in one underground duct, 105°C conductor temperature, 20°C earth ambient temperature.
|
| Application |
| Suitable as a power cable for circuits up to 15000Volts at 133%(ungrounded) insulation level in wet or dry locations at conductor temperatures not exceeding 105°C.
|
| Suitable installations include conduit, trough, open tray, duct, aerial, and direct burial.
|
| Standards |
| UL 1072 for Medium Voltage Cables.
|
| ICEA S-93-639/NEMA WC74 for Shielded Power Cables. (Formerly ICEA S-68-516/NEMA WC8)
|
| AEIC CS-6 for EPR Insulated Shielded Power Cables.
|
| NEC Article 310 & 328 for MV-105 Cable Uses and Constructions.
|
| NEC Article 392 for Cable Tray use.
|
| Optional Constructions |
| PVC jackets on singles.
|
| Hypalon® or CPE outer jacket.
|
|
|