15KV POWER CABLE
THREE CONDUCTOR W/GND SHIELDED EPR O/A PVC JACKET
TYPE MV-105 15KV 133% INSULATION LEVEL

Construction:
CONDUCTOR: CLASS B STRANDED ANNEALED BARE COPPER.
STRAND SHIELD: NONMETALLIC SEMI-CONDUCTING EXTRUDED LAYER.
INSULATION: ETHYLENE PROPYLENE RUBBER (EPR).
INSULATION SHIELDING:
NONMETALLIC LAYER: SEMI-CONDUCTING EXTRUSION DIRECTLY OVER INSULATION.
METALLIC LAYER: LAPPED COPPER TAPE SHIELD DIRECTLY OVER NONMETALLIC LAYER.
CABLE ASSEMBLY: CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND WIRE IN ONE OF THE INTERSTICES, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE.
OVERALL JACKET: SUNLIGHT RESISTANT, BLACK POLYVINYL CHLORIDE (PVC).
 Charlotte Wire Part# ↓   Size AWG   Number of Strands   Insulation Thickness (in.)   Ground Wire Size   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt.   Ampacity in *Duct   Add to Quote Cart 
CW07281 2 7 .220" 6 .110" 2.11" 2290 160 Request Quote For This Product 
CW07282 1 19 .220" 4 .110" 2.15" 2580 185 Request Quote For This Product 
CW07283 1/0 19 .220" 4 .110" 2.25" 2920 210 Request Quote For This Product 
CW07284 2/0 19 .220" 4 .110" 2.34" 3270 235 Request Quote For This Product 
CW07285 3/0 19 .220" 3 .110" 2.45" 3760 270 Request Quote For This Product 
CW07286 4/0 19 .220" 3 .110" 2.58" 4300 305 Request Quote For This Product 
CW07287 250MCM 37 .220" 3 .110" 2.70" 4940 335 Request Quote For This Product 
CW07288 350MCM 37 .220" 2 .140" 2.98" 6280 400 Request Quote For This Product 
CW07289 500MCM 37 .220" 1 .140" 3.25" 8110 485 Request Quote For This Product 
CW07290 750MCM 61 .220" 1/0 .140" 3.68" 11160 585 Request Quote For This Product 
CW07291 1000MCM 61 .220" 1/0 .140" 3.96" 14280 660 Request Quote For This Product 
Displaying 1 to 11 (of 11 products) Result Pages:  1 
* Ampacities are based on 2005 NEC table 310.79, three conductors within overall covering in one underground duct, 105°C conductor temperature, 20°C earth ambient temperature.
Application
Suitable as a power cable for circuits up to 15000Volts at 133%(ungrounded) insulation level in wet or dry locations at conductor temperatures not exceeding 105°C.
Suitable installations include conduit, trough, open tray, duct, aerial, and direct burial.
Standards
UL 1072 for Medium Voltage Cables.
ICEA S-93-639/NEMA WC74 for Shielded Power Cables. (Formerly ICEA S-68-516/NEMA WC8)
AEIC CS-6 for EPR Insulated Shielded Power Cables.
NEC Article 310 & 328 for MV-105 Cable Uses and Constructions.
NEC Article 392 for Cable Tray use.
Optional Constructions
PVC jackets on singles.
Hypalon® or CPE outer jacket.