| 0 items |
 |
|
|
 |
Categories |
 |
|
 |
Part Number Search |
 |
|
 |
Full Search |
 |
|
|
|
 |
2400VOLT POWER CABLE TYPE MV-90
THREE CONDUCTOR WITH GROUND 2400V NONSHIELDED
EPR INSULATION, PVC JACKET
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
CLASS B STRANDED ANNEALED BARE COPPER.
|
| STRAND SHIELD: |
NONMETALLIC SEMI-CONDUCTING EXTRUDED LAYER.
|
| INSULATION: |
ETHYLENE PROPYLENE RUBBER (EPR).
|
| CABLE ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND WIRE IN ONE OF THE INTERSTICES, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, BLACK POLYVINYL CHLORIDE (PVC).
|
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Strands |
Insulation Thickness (in.) |
Ground Wire Size |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Ampacity in *Duct |
Add to Quote Cart |
| CW07151 |
6 |
7 |
.115" |
6 |
.080" |
1.21" |
800 |
78 |
|
| CW07152 |
4 |
7 |
.115" |
6 |
.080" |
1.30" |
1020 |
100 |
|
| CW07153 |
2 |
7 |
.115" |
6 |
.080" |
1.44" |
1290 |
135 |
|
| CW07154 |
1 |
19 |
.115" |
4 |
.080" |
1.52" |
1610 |
155 |
|
| CW07155 |
1/0 |
19 |
.115" |
4 |
.080" |
1.62" |
1880 |
175 |
|
| CW07156 |
2/0 |
19 |
.115" |
4 |
.110" |
1.78" |
2320 |
200 |
|
| CW07157 |
3/0 |
19 |
.115" |
3 |
.110" |
1.89" |
2670 |
230 |
|
| CW07158 |
4/0 |
19 |
.115" |
3 |
.110" |
2.02" |
3280 |
265 |
|
| CW07159 |
250MCM |
37 |
.115" |
3 |
.110" |
2.14" |
3700 |
290 |
|
| CW07160 |
350MCM |
37 |
.115" |
2 |
.110" |
2.36" |
4940 |
355 |
|
| CW07161 |
500MCM |
37 |
.115" |
1 |
.110" |
2.64" |
6610 |
430 |
|
| CW07162 |
750MCM |
61 |
.115" |
1/0 |
.140" |
3.08" |
9510 |
530 |
|
| CW07163 |
1000MCM |
61 |
.115" |
1/0 |
.140" |
3.53" |
12780 |
600 |
|
| Displaying 1 to 13 (of 13 products) |
Result Pages: 1 |
| * Ampacities are based on 2008 NEC table 310.79, three conductors within overall covering in one underground duct, 90°C conductor temperature, 20°C earth ambient temperature.
|
| Application |
| Suitable as a power cable for circuits up to 2400Volts in wet or dry locations at conductor temperatures not exceeding 90°C.
|
| Suitable installations include conduit, trough, open tray, duct, aerial, and direct burial.
|
| Standards |
| UL 1072 for Medium Voltage Cables.
|
| ICEA S-96-659/NEMA WC71 for Nonshielded 2001-5kv cables.
|
| (Formerly ICEA S-68-516/NEMA WC-8)
|
| NEC Article 310 & 328 for MV-90 Cable Uses and Constructions.
|
|
|
|