INTERLOCKED ARMOR CABLE #12AWG
UL TYPE MC, CT USE
XHHW-2 CONDUCTORS, 600VOLTS, 90°C
| Construction: |
| CONDUCTOR: |
7 STRANDED (CLASS B) BARE COPPER. |
| INSULATION: |
THERMOSETTING CROSSLINKED POLYETHYLENE (XLP) TYPE XHHW-2 PER UL 44. |
| CONDUCTORS RATED 90°C WET OR DRY. |
| CONDUCTOR IDENTIFICATION: |
COLOR CODED PER ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532. (FORMERLY K-2). |
| ALSO MAY BE CODED PER ICEA METHOD 4 (BLACK CONDUCTORS WITH NUMBERS). |
| ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND WIRE IN ONE OF THE INTERSTICES, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE. |
| ARMOR: |
ALUMINUM INTERLOCKED ARMOR APPLIED OVER CABLE ASSEMBLY. |
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC APPLIED OVER INTERLOCKED ARMOR. |
| Charlotte Wire Part# ↑ |
Size AWG |
Number of Condr's |
Insulation Thickness (in.) |
Ground Size (AWG) |
Armor Diameter (in.) |
PVC Jkt. thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW08033 |
12 |
37 |
0.03 |
1 - #12 |
1.42" |
.050" |
1.52" |
1420 |
|
| CW08032 |
12 |
30 |
0.03 |
1 - #12 |
1.28" |
.050" |
1.38" |
1210 |
|
| CW08031 |
12 |
25 |
0.03 |
1 - #12 |
1.16" |
.050" |
1.26" |
1040 |
|
| CW08030 |
12 |
20 |
0.03 |
1 - #12 |
1.10" |
.050" |
1.20" |
860 |
|
| CW08029 |
12 |
19 |
0.03 |
1 - #12 |
1.04" |
.050" |
1.14" |
810 |
|
| CW08028 |
12 |
15 |
0.03 |
1 - #12 |
.95" |
.050" |
1.05" |
675 |
|
| CW08027 |
12 |
12 |
0.03 |
1 - #12 |
.87" |
.050" |
.97" |
550 |
|
| CW08026 |
12 |
10 |
0.03 |
1 - #12 |
.81" |
.050" |
.91" |
495 |
|
| CW08025 |
12 |
9 |
0.03 |
1 - #12 |
.79" |
.050" |
.89" |
450 |
|
| CW08024 |
12 |
7 |
0.03 |
1 - #12 |
.69" |
.050" |
.79" |
360 |
|
| CW08023 |
12 |
5 |
0.03 |
1 - #12 |
.65" |
.050" |
.75" |
288 |
|
| CW08022 |
12 |
4 |
0.03 |
1 - #12 |
.62" |
.050" |
.72" |
260 |
|
| CW08021 |
12 |
3 |
0.03 |
1 - #12 |
.60" |
.050" |
.70" |
228 |
|
| CW08020 |
12 |
2 |
0.03 |
1 - #12 |
.59" |
.050" |
.69" |
205 |
|
| Displaying 1 to 14 (of 14 products) |
Result Pages: 1 |
| Application |
| Suitable for power, lighting, control, and signal circuits rated 600Volts. |
| Interlocked armor cables provide excellent corrosion resistance and mechanical protection. |
| May be used as sunlight resistant, directly buried, and wet or dry locations. |
| Per NEC Article 330, may be used |
| 1) indoors (including walls or beams), or outdoors, |
| 2) raceways and cable tray systems including ladders, troughs, and channels, |
| 3) aerial cable on a messenger, and |
| 4) in hazardous locations per NEC Class I Division 2, Class II Division 2, and Class III Division 1. |
| Standards |
| UL Standard 1569 for Type MC Cables. |
| Passes UL & IEEE 70,000BTU Flame Test. |
| UL Standard 44 for XHHW-2 conductors. |
| ICEA S-95-658/NEMA WC70 for Nonshielded 0 - 2KV Cables. Formerly ICEA S-66-524/NEMA WC7). |
| Optional Constructions |
| Inner PVC jacket under armor. |
| Galvanized steel armor. |
| Different colors on outer PVC jacket. |
|
|