INTERLOCKED ARMOR CABLE
3 CONDUCTOR WITH GROUND 600VOLTS
UL TYPE MC, CT USE
XHHW-2 CONDUCTORS, 90°C
| Construction: |
| CONDUCTOR: |
CLASS B STRANDED BARE COPPER. |
| INSULATION: |
THERMOSETTING CROSSLINKED POLYETHYLENE (XLP) TYPE XHHW-2 PER UL 44. |
| CONDUCTORS RATED 90°C WET OR DRY. |
| CONDUCTOR IDENTIFICATION: |
COLOR CODED PER ICEA METHOD 4 (BLACK CONDUCTORS WITH #'S). |
| ALSO MAY BE CODED WITH PAINTED STRIPES ON BLACK CONDUCTORS. |
| ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND WIRE IN ONE OF THE INTERSTICES, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE. |
| ARMOR: |
ALUMINUM INTERLOCKED ARMOR APPLIED OVER CABLE ASSEMBLY. |
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC APPLIED OVER INTERLOCKED ARMOR. |
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Condr's |
Insulation Thickness (in.) |
Ground Size (AWG) |
Armor Diameter (in.) |
PVC Jkt. thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW08056 |
8 |
3 |
0.045 |
1 - #10 |
.75" |
.050" |
.85" |
410 |
|
| CW08057 |
6 |
3 |
0.045 |
1 - #8 |
.84" |
.050" |
.94" |
545 |
|
| CW08058 |
4 |
3 |
0.045 |
1 - #8 |
.92" |
.050" |
1.02" |
746 |
|
| CW08059 |
2 |
3 |
0.045 |
1 - #6 |
1.06" |
.050" |
1.16" |
1070 |
|
| CW08060 |
1 |
3 |
0.055 |
1 - #6 |
1.22" |
.050" |
1.32" |
1290 |
|
| CW08061 |
1/0 |
3 |
0.055 |
1 - #6 |
1.32" |
.050" |
1.42" |
1560 |
|
| CW08062 |
2/0 |
3 |
0.055 |
1 - #6 |
1.42" |
.050" |
1.52" |
1860 |
|
| CW08063 |
3/0 |
3 |
0.055 |
1 - #4 |
1.53" |
.050" |
1.63" |
2350 |
|
| CW08064 |
4/0 |
3 |
0.055 |
1 - #4 |
1.65" |
.060" |
1.77" |
2810 |
|
| CW08065 |
250MCM |
3 |
0.065 |
1 - #4 |
1.81" |
.060" |
1.93" |
3280 |
|
| CW08066 |
350MCM |
3 |
0.065 |
1 - #3 |
2.04" |
.060" |
2.16" |
4420 |
|
| CW08067 |
500MCM |
3 |
0.065 |
1 - #2 |
2.32" |
.075" |
2.47" |
6300 |
|
| CW08068 |
600MCM |
3 |
0.08 |
1 - #1 |
2.50" |
.075" |
2.65" |
7620 |
|
| CW08069 |
750MCM |
3 |
0.08 |
1 - #1 |
2.82" |
.075" |
2.97" |
9060 |
|
| CW08070 |
1000MCM |
3 |
0.08 |
1 - 1/0 |
3.05" |
.085" |
3.22" |
12430 |
|
| Displaying 1 to 15 (of 15 products) |
Result Pages: 1 |
| Application |
| Suitable for power circuits rated up to 600Volts. |
| Interlocked armor cables provide excellent corrosion resistance and mechanical protection. |
| May be used as sunlight resistant, directly buried, and wet or dry locations. |
| Per NEC Article 330, may be used |
| 1) indoors (including walls or beams), or outdoors, |
| 2) raceways and cable tray systems including ladders, troughs, and channels, |
| 3) aerial cable on a messenger, and |
| 4) in hazardous locations per NEC Class I Division 2, Class II Division 2, and Class III Division 1. |
| Standards |
| UL Standard 1569 for Type MC Cables. |
| Passes UL & IEEE 70,000BTU Flame Test. |
| UL Standard 44 for XHHW-2 conductors. |
| ICEA S-95-658/NEMA WC70 for Nonshielded 0 - 2KV Cables. (Formerly ICEA S-66-524/NEMA WC7). |
| Optional Constructions |
| Inner PVC jacket under armor. |
| Different ground wire size(s). |
| Galvanized steel armor. |
| Different colors on outer PVC jacket. |
|
|