INTERLOCKED ARMOR CABLE
4 CONDUCTOR WITH GROUND 600VOLTS
UL TYPE MC, CT USE
XHHW-2 CONDUCTORS, 90°C
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
CLASS B STRANDED BARE COPPER. |
| INSULATION: |
THERMOSETTING CROSSLINKED POLYETHYLENE (XLP) TYPE XHHW-2 PER UL 44. |
| CONDUCTORS RATED 90°C WET OR DRY. |
| CONDUCTOR IDENTIFICATION: |
COLOR CODED PER ICEA METHOD 4 (BLACK CONDUCTORS WITH #'S). |
| ALSO MAY BE CODED WITH PAINTED STRIPES ON BLACK CONDUCTORS. |
| ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND WIRE IN TWO OPPOSITE INTERSTICES, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE. |
| ARMOR: |
ALUMINUM INTERLOCKED ARMOR APPLIED OVER CABLE ASSEMBLY. |
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC APPLIED OVER INTERLOCKED ARMOR. |
| Charlotte Wire Part# ↑ |
Size AWG |
Number of Condr's |
Insulation Thickness (in.) |
Ground Size (AWG) |
Armor Diameter (in.) |
PVC Jkt. thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW08089 |
1000MCM |
4 |
0.08 |
2 - #3 |
3.40" |
.085" |
3.57" |
15940 |
|
| CW08088 |
750MCM |
4 |
0.08 |
2 - #4 |
3.08" |
.085" |
3.25" |
11730 |
|
| CW08087 |
600MCM |
4 |
0.08 |
2 - #5 |
2.80" |
.075" |
2.95" |
9990 |
|
| CW08086 |
500MCM |
4 |
0.065 |
2 - #5 |
2.56" |
.075" |
2.71" |
8120 |
|
| CW08085 |
350MCM |
4 |
0.065 |
2 - #6 |
2.25" |
.060" |
2.37" |
5910 |
|
| CW08084 |
250MCM |
4 |
0.065 |
2 - #7 |
2.00" |
.060" |
2.12" |
4165 |
|
| CW08083 |
4/0 |
4 |
0.055 |
2 - #7 |
1.85" |
.060" |
1.97" |
3650 |
|
| CW08082 |
3/0 |
4 |
0.055 |
2 - #7 |
1.70" |
.060" |
1.82" |
2940 |
|
| CW08081 |
2/0 |
4 |
0.055 |
2 - #9 |
1.58" |
.050" |
1.68" |
2395 |
|
| CW08080 |
1/0 |
4 |
0.055 |
2 - #9 |
1.46" |
.050" |
1.56" |
2010 |
|
| CW08079 |
1 |
4 |
0.055 |
2 - #9 |
1.37" |
.050" |
1.47" |
1690 |
|
| CW08078 |
2 |
4 |
0.045 |
2 - #9 |
1.16" |
.050" |
1.26" |
1340 |
|
| CW08077 |
4 |
4 |
0.045 |
2 - #10 |
1.02" |
.050" |
1.12" |
930 |
|
| CW08076 |
6 |
4 |
0.045 |
2 - #10 |
.92" |
.050" |
1.02" |
680 |
|
| CW08075 |
8 |
4 |
0.045 |
2 - #12 |
.82" |
.050" |
.92" |
500 |
|
| Displaying 1 to 15 (of 15 products) |
Result Pages: 1 |
| Application |
| Suitable for power circuits rated up to 600Volts. |
| Interlocked armor cables provide excellent corrosion resistance and mechanical protection. |
| May be used as sunlight resistant, directly buried, and wet or dry locations. |
| Per NEC Article 330, may be used |
| 1) indoors (including walls or beams), or outdoors, |
| 2) raceways and cable tray systems including ladders, troughs, and channels, |
| 3) aerial cable on a messenger, and |
| 4) in hazardous locations per NEC Class I Division 2, Class II Division 2, and Class III Division 1. |
| Standards |
| UL Standard 1569 for Type MC Cables. |
| Passes UL & IEEE 70,000BTU Flame Test. |
| UL Standard 44 for XHHW-2 conductors. |
| ICEA S-95-658/NEMA WC70 for Nonshielded 0 - 2KV Cables. (Formerly ICEA S-66-524/NEMA WC7). |
| Optional Constructions |
| Inner PVC jacket under armor. |
| Larger ground wire(s). |
| Galvanized steel armor. |
| Different colors on outer PVC jacket. |
|