TECK90 INTERLOCKED ARMOR CABLE #10AWG
CSA 22.2 FT4, HL
XLP INSULATION, 600VOLTS, -40°C TO 90°C
| Construction: |
| CONDUCTOR: |
7 STRANDED (CLASS B) SOFT DRAWN BARE COPPER.
|
| INSULATION: |
THERMOSETTING CROSSLINKED POLYETHYLENE (XLP).
|
| ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND WIRE, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE WHERE NECESSARY.
|
| ARMOR: |
ALUMINUM INTERLOCKED ARMOR APPLIED OVER INNER PVC JACKET.
|
| INNER PVC JACKET: |
POLYVINYL CHLORIDE (PVC) APPLIED OVER CABLE ASSEMBLY.
|
| OUTER PVC JACKET: |
BLACK POLYVINYL CHLORIDE APPLIED OVER ARMOR.
|
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Condr's |
Insulation Thickness (in.) |
Ground Size (AWG) |
Inner Jacket Diameter |
Over Armor Diameter |
Outer Jacket Diameter |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW08361 |
10 |
2 |
0.03 |
1 - #12 |
.46" |
.66" |
.77" |
282 |
|
| CW08362 |
10 |
3 |
0.03 |
1 - #12 |
.49" |
.69" |
.80" |
328 |
|
| CW08363 |
10 |
4 |
0.03 |
1 - #12 |
.56" |
.76" |
.87" |
395 |
|
| CW08364 |
10 |
5 |
0.03 |
1 - #12 |
.63" |
.83" |
.94" |
475 |
|
| CW08365 |
10 |
6 |
0.03 |
1 - #12 |
.67" |
.87" |
.98" |
530 |
|
| CW08366 |
10 |
7 |
0.03 |
1 - #12 |
.69" |
.89" |
1.01" |
580 |
|
| CW08367 |
10 |
8 |
0.03 |
1 - #12 |
.76" |
.96" |
1.08" |
685 |
|
| CW08368 |
10 |
9 |
0.03 |
1 - #12 |
.80" |
1.00" |
1.12" |
730 |
|
| CW08369 |
10 |
10 |
0.03 |
1 - #12 |
.86" |
1.07" |
1.18" |
790 |
|
| CW08370 |
10 |
12 |
0.03 |
1 - #12 |
.94" |
1.16" |
1.27" |
950 |
|
| CW08371 |
10 |
15 |
0.03 |
1 - #12 |
1.04" |
1.25" |
1.36" |
1080 |
|
| CW08372 |
10 |
19 |
0.03 |
1 - #12 |
1.14" |
1.36" |
1.47" |
1310 |
|
| CW08373 |
10 |
20 |
0.03 |
1 - #12 |
1.16" |
1.38" |
1.49" |
1370 |
|
| CW08374 |
10 |
25 |
0.03 |
1 - #12 |
1.28" |
1.51" |
1.62" |
1600 |
|
| CW08375 |
10 |
30 |
0.03 |
1 - #12 |
1.36" |
1.58" |
1.70" |
1875 |
|
| CW08376 |
10 |
40 |
0.03 |
1 - #12 |
1.54" |
1.77" |
1.90" |
2370 |
|
| CW08377 |
10 |
50 |
0.03 |
1 - #12 |
1.72" |
1.96" |
2.09" |
2900 |
|
| Displaying 1 to 17 (of 17 products) |
Result Pages: 1 |
| Application |
| Suitable for power, lighting, control, and signal circuits up to 600Volts in a variety of industrial locations including pulp and paper, chemical, petrochemical, and mines.
|
| Areas for use are
|
| 1) wet or dry locations,
|
| 2) ventilated, nonventilated, and ladder type cable trays, and
|
| 3) direct burial.
|
| Standards |
| CSA Standard 22.2 for TECK90 Cables.
|
| Passes CSA FT4 Flame Test.
|
| HL Rating per CSA 22.2.
|
| Optional Constructions |
| Galvanized Steel Armor.
|
| UL Type MC.
|
| Different colors on outer pvc jacket.
|
| Different conductor color code.
|
| Conductor Identification |
| NO. of CONDUCTORS |
IDENTIFICATION
|
| 2 |
Black, White
|
| 3 |
Black, Red, Blue
|
| 4 |
Black, Red, Blue, White
|
| 5 or more |
Number Coded
|
|
|