TECK90 INTERLOCKED ARMOR CABLE 3/C
CSA 22.2 FT4, HL
XLP INSULATION, 1000VOLTS, -40°C TO 90°C
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
7 STRANDED (CLASS B) SOFT DRAWN BARE COPPER.
|
| INSULATION: |
THERMOSETTING CROSSLINKED POLYETHYLENE (XLP).
|
| ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND WIRE, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE WHERE NECESSARY.
|
| ARMOR: |
ALUMINUM INTERLOCKED ARMOR APPLIED OVER INNER PVC JACKET.
|
| INNER PVC JACKET: |
POLYVINYL CHLORIDE (PVC) APPLIED OVER CABLE ASSEMBLY.
|
| OUTER PVC JACKET: |
BLACK POLYVINYL CHLORIDE APPLIED OVER ARMOR.
|
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Condr's |
Insulation Thickness (in.) |
Ground Size (AWG) |
Inner Jacket Diameter |
Over Armor Diameter |
Outer Jacket Diameter |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW08401 |
14 |
3 |
0.045 |
1 - #14 |
.47" |
.67" |
.77" |
255 |
|
| CW08402 |
12 |
3 |
0.045 |
1 - #14 |
.52" |
.72" |
.82" |
295 |
|
| CW08403 |
10 |
3 |
0.045 |
1 - #12 |
.59" |
.79" |
.89" |
385 |
|
| CW08404 |
8 |
3 |
0.045 |
1 - #10 |
.66" |
.86" |
.96" |
488 |
|
| CW08405 |
6 |
3 |
0.06 |
1 - #8 |
.79" |
.99" |
1.10" |
675 |
|
| CW08406 |
4 |
3 |
0.06 |
1 - #8 |
.93" |
1.13" |
1.25" |
970 |
|
| CW08407 |
2 |
3 |
0.06 |
1 - #6 |
1.07" |
1.27" |
1.38" |
1296 |
|
| CW08408 |
1 |
3 |
0.08 |
1 - #6 |
1.22" |
1.42" |
1.53" |
1640 |
|
| CW08409 |
1/0 |
3 |
0.08 |
1 - #6 |
1.30" |
1.52" |
1.63" |
1880 |
|
| CW08410 |
2/0 |
3 |
0.08 |
1 - #6 |
1.37" |
1.58" |
1.70" |
2250 |
|
| CW08411 |
3/0 |
3 |
0.08 |
1 - #4 |
1.48" |
1.69" |
1.82" |
2700 |
|
| CW08412 |
4/0 |
3 |
0.08 |
1 - #4 |
1.59" |
1.84" |
1.97" |
3260 |
|
| CW08413 |
250MCM |
3 |
0.09 |
1 - #4 |
1.81" |
2.06" |
2.19" |
3800 |
|
| CW08414 |
350MCM |
3 |
0.09 |
1 - #3 |
2.02" |
2.27" |
2.40" |
4980 |
|
| CW08415 |
500MCM |
3 |
0.09 |
1 - #3 |
2.28" |
2.52" |
2.67" |
6790 |
|
| CW08416 |
750MCM |
3 |
0.09 |
1 - #2 |
2.70" |
2.95" |
3.12" |
9600 |
|
| CW08417 |
1000MCM |
3 |
0.09 |
1 - #1 |
3.09" |
3.34" |
3.50" |
12800 |
|
| Displaying 1 to 17 (of 17 products) |
Result Pages: 1 |
| Application |
| Suitable for power, lighting, control, and signal circuits up to 1000Volts in a variety of industrial locations including pulp and paper, chemical, petrochemical, and mines.
|
| Areas for use are
|
| 1) wet or dry locations,
|
| 2) ventilated, nonventilated, and ladder type cable trays, and
|
| 3) direct burial.
|
| Standards |
| CSA Standard 22.2 for TECK90 Cables.
|
| Passes CSA FT4 Flame Test.
|
| HL Rating per CSA 22.2.
|
| Optional Constructions |
| Galvanized Steel Armor.
|
| UL Type MC.
|
| Different colors on outer pvc jacket.
|
| Different conductor color code.
|
| Conductor Identification |
| CONDUCTOR SIZE |
IDENTIFICATION
|
| 14AWG through 2AWG |
Black, Red, Blue
|
| 1AWG through 1000MCM |
Number Coded
|
|