CONTINUOUS CORRUGATED ARMOR CABLE
3 CONDUCTORS WITH 3 GROUNDS 600VOLTS
AC DRIVE CABLE, UL TYPE MC-HL , CT USE
XHHW-2 CONDUCTORS, 90°C WET OR DRY

Construction:
CONDUCTOR: CLASS B STRANDED BARE COPPER.
INSULATION: THERMOSETTING CROSSLINKED POLYETHYLENE (XLP) XHHW-2.
CONDUCTOR IDENTIFICATION: COLOR CODED PER ICEA METHOD 4(BLACK WITH PRINTED NUMBERS) ON SIZES #8AWG AND LARGER.
SIZES 14 THROUGH 10AWG CODED PER ICEA S-73-532 METHOD 1 TABLE E-2. (BLACK - RED - BLUE).
ASSEMBLY: CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND WIRE IN EACH INTERSTICE, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE.
ARMOR: CONTINUOUS CORRUGATED ALUMINUM ARMOR WHICH IS IMPERVIOUS TO LIQUIDS, MOISTURE, AND GASES.
OVERALL JACKET: SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC APPLIED OVER ARMOR.
 Charlotte Wire Part# ↑   Size AWG   Number of Condr's   Insulation Thickness (in.)   Ground Sizes (AWG)   Armor Diameter   PVC Jkt Thickness )in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW08566 750MCM 3 0.08 3 - #5 3.05" .085" 3.20" 9380 Request Quote For This Product 
CW08565 500MCM 3 0.065 3 - #6 2.46" .075" 2.60" 6190 Request Quote For This Product 
CW08564 350MCM 3 0.065 3 - #7 2.21" .060" 2.34" 4500 Request Quote For This Product 
CW08563 250MCM 3 0.065 3 - #8 1.98" .060" 2.10" 3400 Request Quote For This Product 
CW08562 4/0 3 0.055 3 - #8 1.76" .060" 1.90" 2890 Request Quote For This Product 
CW08561 3/0 3 0.055 3 - #8 1.60" .060" 1.74" 2390 Request Quote For This Product 
CW08560 2/0 3 0.055 3 - #10 1.56" .050" 1.69" 1920 Request Quote For This Product 
CW08559 1/0 3 0.055 3 - #10 1.38" .050" 1.48" 1610 Request Quote For This Product 
CW08558 1 3 0.055 3 - #10 1.30" .050" 1.40" 1300 Request Quote For This Product 
CW08557 2 3 0.045 3 - #10 1.13" .050" 1.24" 1090 Request Quote For This Product 
CW08556 4 3 0.045 3 - #12 .97" .050" 1.08" 756 Request Quote For This Product 
CW08555 6 3 0.045 3 - #12 .84" .050" .95" 562 Request Quote For This Product 
CW08554 8 3 0.045 3 - #14 .76" .050" .87" 422 Request Quote For This Product 
CW08553 10 3 0.03 3 - #14 .62" .050" .73" 315 Request Quote For This Product 
CW08552 12 3 0.03 3 - #16 .57" .050" .68" 230 Request Quote For This Product 
CW08551 14 3 0.03 3 - #18 .53" .050" .63" 180 Request Quote For This Product 
Displaying 1 to 16 (of 16 products) Result Pages:  1 
Application
Suitable for power, lighting, control, and signal circuits in a variety of industrial locations including pulp and paper, chemical, and petrochemical.
Continuous corrugated armor provides excellent mechanical resistance and can be used as an electrical shield when adequate grounding is maintained.
The armor shield capability along with the 3 symmetrical grounds provides an excellent cable for AC Drive applications.
Per NEC Art. 300, may be used
1) indoors or outdoors,
2) in raceway or cable tray,
3) as aerial cable cable on a messenger,
4) in direct burial applications, and
5) in hazardous locations per NEC Class I, II, and III, Divisions 1 and 2.
Standards
UL Standard 1569 for Type MC Cables.
Passes UL & IEEE 70,000BTU Flame Test.
UL Standard 44 for XHHW-2 conductors.
ICEA S-95-658/NEMA WC70 for Nonshielded 0 - 2KV Cables. (Formerly ICEA S-66-524/NEMA WC7).
NEC Article 330 for Metal Clad Uses and Constructions.
UL Standard 2225 for Metal Clad Cables in Hazardous Locations.