CONTINUOUS CORRUGATED ARMOR CABLE
3 CONDUCTORS WITH 3 GROUNDS 600VOLTS
AC DRIVE CABLE, UL TYPE MC-HL , CT USE
XHHW-2 CONDUCTORS, 90°C WET OR DRY
| Construction: |
| CONDUCTOR: |
CLASS B STRANDED BARE COPPER.
|
| INSULATION: |
THERMOSETTING CROSSLINKED POLYETHYLENE (XLP) XHHW-2.
|
| CONDUCTOR IDENTIFICATION: |
COLOR CODED PER ICEA METHOD 4(BLACK WITH PRINTED NUMBERS) ON SIZES #8AWG AND LARGER.
|
| SIZES 14 THROUGH 10AWG CODED PER ICEA S-73-532 METHOD 1 TABLE E-2. (BLACK - RED - BLUE).
|
| ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND WIRE IN EACH INTERSTICE, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE.
|
| ARMOR: |
CONTINUOUS CORRUGATED ALUMINUM ARMOR WHICH IS IMPERVIOUS TO LIQUIDS, MOISTURE, AND GASES.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC APPLIED OVER ARMOR.
|
| Charlotte Wire Part# ↑ |
Size AWG |
Number of Condr's |
Insulation Thickness (in.) |
Ground Sizes (AWG) |
Armor Diameter |
PVC Jkt Thickness )in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW08566 |
750MCM |
3 |
0.08 |
3 - #5 |
3.05" |
.085" |
3.20" |
9380 |
|
| CW08565 |
500MCM |
3 |
0.065 |
3 - #6 |
2.46" |
.075" |
2.60" |
6190 |
|
| CW08564 |
350MCM |
3 |
0.065 |
3 - #7 |
2.21" |
.060" |
2.34" |
4500 |
|
| CW08563 |
250MCM |
3 |
0.065 |
3 - #8 |
1.98" |
.060" |
2.10" |
3400 |
|
| CW08562 |
4/0 |
3 |
0.055 |
3 - #8 |
1.76" |
.060" |
1.90" |
2890 |
|
| CW08561 |
3/0 |
3 |
0.055 |
3 - #8 |
1.60" |
.060" |
1.74" |
2390 |
|
| CW08560 |
2/0 |
3 |
0.055 |
3 - #10 |
1.56" |
.050" |
1.69" |
1920 |
|
| CW08559 |
1/0 |
3 |
0.055 |
3 - #10 |
1.38" |
.050" |
1.48" |
1610 |
|
| CW08558 |
1 |
3 |
0.055 |
3 - #10 |
1.30" |
.050" |
1.40" |
1300 |
|
| CW08557 |
2 |
3 |
0.045 |
3 - #10 |
1.13" |
.050" |
1.24" |
1090 |
|
| CW08556 |
4 |
3 |
0.045 |
3 - #12 |
.97" |
.050" |
1.08" |
756 |
|
| CW08555 |
6 |
3 |
0.045 |
3 - #12 |
.84" |
.050" |
.95" |
562 |
|
| CW08554 |
8 |
3 |
0.045 |
3 - #14 |
.76" |
.050" |
.87" |
422 |
|
| CW08553 |
10 |
3 |
0.03 |
3 - #14 |
.62" |
.050" |
.73" |
315 |
|
| CW08552 |
12 |
3 |
0.03 |
3 - #16 |
.57" |
.050" |
.68" |
230 |
|
| CW08551 |
14 |
3 |
0.03 |
3 - #18 |
.53" |
.050" |
.63" |
180 |
|
| Displaying 1 to 16 (of 16 products) |
Result Pages: 1 |
| Application |
| Suitable for power, lighting, control, and signal circuits in a variety of industrial locations including pulp and paper, chemical, and petrochemical.
|
| Continuous corrugated armor provides excellent mechanical resistance and can be used as an electrical shield when adequate grounding is maintained.
|
| The armor shield capability along with the 3 symmetrical grounds provides an excellent cable for AC Drive applications.
|
| Per NEC Art. 300, may be used
|
| 1) indoors or outdoors,
|
| 2) in raceway or cable tray,
|
| 3) as aerial cable cable on a messenger,
|
| 4) in direct burial applications, and
|
| 5) in hazardous locations per NEC Class I, II, and III, Divisions 1 and 2.
|
| Standards |
| UL Standard 1569 for Type MC Cables.
|
| Passes UL & IEEE 70,000BTU Flame Test.
|
| UL Standard 44 for XHHW-2 conductors.
|
| ICEA S-95-658/NEMA WC70 for Nonshielded 0 - 2KV Cables. (Formerly ICEA S-66-524/NEMA WC7).
|
| NEC Article 330 for Metal Clad Uses and Constructions.
|
| UL Standard 2225 for Metal Clad Cables in Hazardous Locations.
|
|
|