INTERLOCKED ARMOR CABLE
3 CONDUCTOR W/GROUND 2400VOLT NONSHIELDED
EPR INSULATION , 90°C
UL TYPE MC, MV-90, CT USE

Construction:
CONDUCTOR: CLASS B STRANDED BARE COPPER.
INSULATION: THERMOSETTING ETHYLENE PROPYLENE RUBBER (EPR).
CONDUCTOR IDENTIFICATION: PHASE CODED WITH SUITABLE MARKING ON EACH CONDUCTOR.
CONDUCTOR ASSEMBLY: CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND IN ONE OF THE INTERSTICES, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE.
ARMOR: ALUMINUM INTERLOCKED ARMOR APPLIED OVER CABLE ASSEMBLY.
STRAND SHIELD: EXTRUDED NONMETALLIC SEMI-CONDUCTING LAYER.
OVERALL JACKET: SUNLIGHT RESISTANT, FLAME RETARDANT YELLOW PVC APPLIED OVER INTERLOCKED ARMOR.
 Charlotte Wire Part# ↓   Size AWG   Insulation Thickness (in.)   Ground Size (AWG)   Armor Diameter (in.)   PVC Jkt Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Amps *   Add to Quote Cart 
CW08601 8 0.115" 1 - #8 1.06" 0.050" 1.16" 650 52 Request Quote For This Product 
CW08602 6 0.115" 1 - #6 1.20" 0.050" 1.30" 895 69 Request Quote For This Product 
CW08603 4 0.115" 1 - #6 1.30" 0.050" 1.40" 1120 91 Request Quote For This Product 
CW08604 2 0.115" 1 - #6 1.44" 0.050" 1.54" 1440 125 Request Quote For This Product 
CW08605 1 0.115" 1 - #4 1.49" 0.050" 1.59" 1760 140 Request Quote For This Product 
CW08606 1/0 0.115" 1 - #4 1.60" 0.060" 1.72" 2040 165 Request Quote For This Product 
CW08607 2/0 0.115" 1 - #4 1.74" 0.060" 1.86" 2400 190 Request Quote For This Product 
CW08608 3/0 0.115" 1 - #3 1.81" 0.060" 1.93" 2960 220 Request Quote For This Product 
CW08609 4/0 0.115" 1 - #3 1.97" 0.060" 2.09" 3410 255 Request Quote For This Product 
CW08610 250MCM 0.115" 1 - #3 2.06" 0.060" 2.18" 3870 280 Request Quote For This Product 
CW08611 350MCM 0.115" 1 - #2 2.32" 0.075" 2.47" 5120 350 Request Quote For This Product 
CW08612 500MCM 0.115" 1 - #1 2.60" 0.075" 2.75" 6850 425 Request Quote For This Product 
CW08613 750MCM 0.115" 1 - 1/0 3.00" 0.075" 3.15" 9880 525 Request Quote For This Product 
CW08614 1000MCM 0.115" 1 - 1/0 3.30" 0.085" 3.47" 13000 590 Request Quote For This Product 
Displaying 1 to 14 (of 14 products) Result Pages:  1 
Application
Suitable for power circuits rated up to 2400Volts in industrial, commercial, and utility locations.
Per NEC Article 330, may be used
1) indoors or outdoors,
2) raceways and cable tray systems including ladders, troughs, and channels,
3) aerial cable on a messenger, and
4) in hazardous locations per NEC Class 1 Division 2, Class II Division 2, and Class III Division 1 and 2.
Standards
UL Standard 1569 for Type MC Cables.
Passes UL & IEEE 70,000BTU Flame Test.
ICEA S-96-659/NEMA WC71 for Nonshielded 2001-5KV Cables. (Formerly ICEA S-68-516/NEMA WC 8).
UL 1072 for Medium Voltage Cables.
NEC Article 330 for Metal Clad Cables.