INTERLOCKED ARMOR CABLE
3 CONDUCTOR W/GROUND 2400VOLT NONSHIELDED
EPR INSULATION , 90°C
UL TYPE MC, MV-90, CT USE
| Construction: |
| CONDUCTOR: |
CLASS B STRANDED BARE COPPER.
|
| INSULATION: |
THERMOSETTING ETHYLENE PROPYLENE RUBBER (EPR).
|
| CONDUCTOR IDENTIFICATION: |
PHASE CODED WITH SUITABLE MARKING ON EACH CONDUCTOR.
|
| CONDUCTOR ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND IN ONE OF THE INTERSTICES, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE.
|
| ARMOR: |
ALUMINUM INTERLOCKED ARMOR APPLIED OVER CABLE ASSEMBLY.
|
| STRAND SHIELD: |
EXTRUDED NONMETALLIC SEMI-CONDUCTING LAYER.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT YELLOW PVC APPLIED OVER INTERLOCKED ARMOR.
|
| Charlotte Wire Part# ↓ |
Size AWG |
Insulation Thickness (in.) |
Ground Size (AWG) |
Armor Diameter (in.) |
PVC Jkt Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Amps * |
Add to Quote Cart |
| CW08601 |
8 |
0.115" |
1 - #8 |
1.06" |
0.050" |
1.16" |
650 |
52 |
|
| CW08602 |
6 |
0.115" |
1 - #6 |
1.20" |
0.050" |
1.30" |
895 |
69 |
|
| CW08603 |
4 |
0.115" |
1 - #6 |
1.30" |
0.050" |
1.40" |
1120 |
91 |
|
| CW08604 |
2 |
0.115" |
1 - #6 |
1.44" |
0.050" |
1.54" |
1440 |
125 |
|
| CW08605 |
1 |
0.115" |
1 - #4 |
1.49" |
0.050" |
1.59" |
1760 |
140 |
|
| CW08606 |
1/0 |
0.115" |
1 - #4 |
1.60" |
0.060" |
1.72" |
2040 |
165 |
|
| CW08607 |
2/0 |
0.115" |
1 - #4 |
1.74" |
0.060" |
1.86" |
2400 |
190 |
|
| CW08608 |
3/0 |
0.115" |
1 - #3 |
1.81" |
0.060" |
1.93" |
2960 |
220 |
|
| CW08609 |
4/0 |
0.115" |
1 - #3 |
1.97" |
0.060" |
2.09" |
3410 |
255 |
|
| CW08610 |
250MCM |
0.115" |
1 - #3 |
2.06" |
0.060" |
2.18" |
3870 |
280 |
|
| CW08611 |
350MCM |
0.115" |
1 - #2 |
2.32" |
0.075" |
2.47" |
5120 |
350 |
|
| CW08612 |
500MCM |
0.115" |
1 - #1 |
2.60" |
0.075" |
2.75" |
6850 |
425 |
|
| CW08613 |
750MCM |
0.115" |
1 - 1/0 |
3.00" |
0.075" |
3.15" |
9880 |
525 |
|
| CW08614 |
1000MCM |
0.115" |
1 - 1/0 |
3.30" |
0.085" |
3.47" |
13000 |
590 |
|
| Displaying 1 to 14 (of 14 products) |
Result Pages: 1 |
| Application |
| Suitable for power circuits rated up to 2400Volts in industrial, commercial, and utility locations.
|
| Per NEC Article 330, may be used
|
| 1) indoors or outdoors,
|
| 2) raceways and cable tray systems including ladders, troughs, and channels,
|
| 3) aerial cable on a messenger, and
|
| 4) in hazardous locations per NEC Class 1 Division 2, Class II Division 2, and Class III Division 1 and 2.
|
| Standards |
| UL Standard 1569 for Type MC Cables.
|
| Passes UL & IEEE 70,000BTU Flame Test.
|
| ICEA S-96-659/NEMA WC71 for Nonshielded 2001-5KV Cables. (Formerly ICEA S-68-516/NEMA WC 8).
|
| UL 1072 for Medium Voltage Cables.
|
| NEC Article 330 for Metal Clad Cables.
|
|
|