INTERLOCKED ARMOR CABLE
3 CONDUCTOR W/GROUND 15KV SHIELDED
EPR INSULATION , 133% INSULATION LEVEL
UL TYPE MC , MV-105 , CT USE

Construction:
CONDUCTOR: CLASS B STRANDED BARE COPPER.
INSULATION: THERMOSETTING ETHYLENE PROPYLENE RUBBER (EPR).
CONDUCTOR IDENTIFICATION: PHASE CODED WITH SUITABLE MARKING ON EACH CONDUCTOR.
CONDUCTOR ASSEMBLY: CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND IN ONE OF THE INTERSTICES, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE.
ARMOR: ALUMINUM INTERLOCKED ARMOR APPLIED OVER CABLE ASSEMBLY.
STRAND SHIELD: EXTRUDED NONMETALLIC SEMI-CONDUCTING LAYER.
INSULATION SHIELDING:
NONMETALLIC LAYER: SEMI-CONDUCTING LAYER DIRECTLY OVER INSULATION.
METALLIC LAYER: LAPPED COPPER TAPE DIRECTLY OVER NONMETALLIC LAYER.
OVERALL JACKET: SUNLIGHT RESISTANT, FLAME RETARDANT RED PVC APPLIED OVER INTERLOCKED ARMOR.
 Charlotte Wire Part# ↓   Size AWG   Insulation Thickness (in.)   Ground Size (AWG)   Armor Diameter (in.)   PVC Jkt Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Amps *   Add to Quote Cart 
CW08701 2 0.22" 1 - #6 2.13" 0.060" 2.25" 2580 165 Request Quote For This Product 
CW08702 1 0.22" 1 - #4 2.22" 0.060" 2.34" 2800 185 Request Quote For This Product 
CW08703 1/0 0.22" 1 - #4 2.32" 0.060" 2.44" 3160 215 Request Quote For This Product 
CW08704 2/0 0.22" 1 - #4 2.41" 0.075" 2.56" 3590 245 Request Quote For This Product 
CW08705 3/0 0.22" 1 - #3 2.52" 0.075" 2.67" 4000 280 Request Quote For This Product 
CW08706 4/0 0.22" 1 - #3 2.65" 0.075" 2.80" 4640 320 Request Quote For This Product 
CW08707 250MCM 0.22" 1 - #3 2.78" 0.075" 2.93" 5300 350 Request Quote For This Product 
CW08708 350MCM 0.22" 1 - #2 3.02" 0.075" 3.17" 6620 430 Request Quote For This Product 
CW08709 500MCM 0.22" 1 - #1 3.31" 0.085" 3.48" 8690 525 Request Quote For This Product 
CW08710 750MCM 0.22" 1 - 1/0 3.70" 0.085" 3.87" 11900 635 Request Quote For This Product 
CW08711 1000MCM 0.22" 1 - 1/0 4.06" 0.085" 4.23" 14850 725 Request Quote For This Product 
Displaying 1 to 11 (of 11 products) Result Pages:  1 
* Ampacity based on 3 conductor in isolated conduit in air with 105°C conductor temperature and 40°C ambient temperature per 2002 NEC Table 310.75.
Application
Suitable for power circuits rated up to 15000Volts 133% Insulation Level (ungrounded) in industrtial, commercial, and utility locations.
Per NEC Article 330, may be used
1) indoors or outdoors,
2) raceways and cable tray systems including ladders, troughs, and channels,
3) aerial cable on a messenger, and
4) in hazardous locations per NEC Class 1 Division 2, Class II Division 2, and Class III Division 1 and 2.
Standards
Passes UL & IEEE 70,000BTU Flame Test.
ICEA S-93-639/NEMA WC74 for Shielded Power Cables. (Formerly ICEA S-68-516/NEMA WC-8).
UL 1072 for Medium Voltage Cables.
NEC Article 330 for Metal Clad Cable.
NEC Article 392 for Tray Use.
Optional Constructions
XLP insulation.
PVC jackets on singles.
Different ground wire sizes.
Galvanized steel armor.
Different colors on outer PVC jacket.