INTERLOCKED ARMOR CABLE
3 CONDUCTOR W/GROUND 5KV SHIELDED
EPR INSULATION , 133% INSULATION LEVEL
UL TYPE MC , MV-105 , CT USE
| Construction: |
| CONDUCTOR: |
CLASS B STRANDED BARE COPPER.
|
| STRAND SHIELD: |
EXTRUDED NONMETALLIC SEMI-CONDUCTING LAYER.
|
| INSULATION: |
THERMOSETTING ETHYLENE PROPYLENE RUBBER (EPR).
|
| INSULATION SHIELDING:
|
| NONMETALLIC LAYER: |
SEMI-CONDUCTING LAYER DIRECTLY OVER INSULATION.
|
| METALLIC LAYER: |
LAPPED COPPER TAPE DIRECTLY OVER NONMETALLIC LAYER.
|
| CONDUCTOR IDENTIFICATION: |
PHASE CODED WITH SUITABLE MARKING ON EACH CONDUCTOR.
|
| CONDUCTOR ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND IN ONE OF THE INTERSTICES, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE.
|
| ARMOR: |
ALUMINUM INTERLOCKED ARMOR APPLIED OVER CABLE ASSEMBLY.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT YELLOW PVC APPLIED OVER INTERLOCKED ARMOR.
|
| Charlotte Wire Part# ↓ |
Size AWG |
Insulation Thickness (in.) |
Ground Size (AWG) |
Armor Diameter (in.) |
PVC Jkt Thickness (in.) |
Approx. Net Wt. (Lbs/Mft) |
Amps * |
Add to Quote Cart |
| CW08621 |
6 |
.115" |
1-#6 |
1.49" |
.050" |
1280 |
88 |
|
| CW08622 |
4 |
.115" |
1-#6 |
1.56" |
.050" |
1390 |
115 |
|
| CW08623 |
2 |
.115" |
1-#6 |
1.77" |
.060" |
1810 |
154 |
|
| CW08624 |
1 |
.115" |
1-#4 |
1.84" |
.060" |
2080 |
180 |
|
| CW08625 |
1/0 |
.115" |
1-#4 |
1.98" |
.060" |
2400 |
205 |
|
| CW08626 |
2/0 |
.115" |
1-#4 |
2.07" |
.060" |
2750 |
240 |
|
| CW08627 |
3/0 |
.115" |
1-#3 |
2.18" |
.060" |
3100 |
280 |
|
| CW08628 |
4/0 |
.115" |
1-#3 |
2.33" |
.060" |
3720 |
320 |
|
| CW08629 |
250MCM |
.115" |
1-#3 |
2.44" |
.075" |
4240 |
355 |
|
| CW08630 |
350MCM |
.115" |
1-#2 |
2.65" |
.075" |
5610 |
440 |
|
| CW08631 |
500MCM |
.115" |
1-#1 |
2.95" |
.075" |
7640 |
545 |
|
| CW08632 |
750MCM |
.115" |
1-1/0 |
3.38" |
.085" |
10640 |
685 |
|
| CW08633 |
1000MCM |
.115" |
1-1/0 |
3.82" |
.085" |
13750 |
790 |
|
| Displaying 1 to 13 (of 13 products) |
Result Pages: 1 |
| * Ampacity based on 3 conductor isolated in air with 105°C conductor temperature and 40°C ambient temperature per 2005 NEC Table 310.71.
|
| Application |
| Suitable for power circuits rated up to 5000Volts 133% Insulation Level (ungrounded) in industrial, commercial, and utility locations.
|
| Per NEC Article 330, may be used
|
| 1) indoors or outdoors,
|
| 2) raceways and cable tray systems including ladders, troughs, and channels,
|
| 3) aerial cable on a messenger, and
|
| 4) in hazardous locations per NEC Class 1 Division 2, Class II Division 2, and Class III Division 1 and 2.
|
| Standards |
| Passes UL & IEEE 70,000BTU Flame Test.
|
| ICEA S-93-639/NEMA WC74 for Shielded Power Cables. (Formerly ICEA S-68-516/NEMA WC-8).
|
| UL 1072 for Medium Voltage Cables.
|
| NEC Article 330 for Metal Clad Cable.
|
| NEC Article 392 for Tray Use.
|
|
|