CONTINUOUS CORRUGATED ARMOR CABLE
4 CONDUCTORS WITH GROUND 600VOLTS
UL TYPE MC-HL, CT USE
XHHW-2 CONDUCTORS, 90°C WET OR DRY
| Construction: |
| CONDUCTOR: |
CLASS B STRANDED BARE COPPER.
|
| INSULATION: |
THERMOSETTING CROSSLINKED POLYETHYLENE (XLP) XHHW-2.
|
| CONDUCTOR IDENTIFICATION: |
COLOR CODED PER ICEA METHOD 4(BLACK WITH PRINTED NUMBERS).
|
| ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND WIRE IN ONE INTERSTICE, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE.
|
| ARMOR: |
CONTINUOUS CORRUGATED ALUMINUM ARMOR WHICH IS IMPERVIOUS TO LIQUIDS, MOISTURE, AND GASES.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC APPLIED OVER ARMOR.
|
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Condr's |
Insulation Thickness (in.) |
Ground Sizes (AWG) |
Armor Diameter |
PVC Jkt Thickness )in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW08571 |
8 |
4 |
.045" |
1 - #10 |
0.80" |
.050" |
0.90" |
480 |
|
| CW08572 |
6 |
4 |
.045" |
1 - #8 |
0.96" |
.050" |
1.06" |
680 |
|
| CW08573 |
4 |
4 |
.045" |
1 - #8 |
1.15" |
.050" |
1.25" |
950 |
|
| CW08574 |
2 |
4 |
.045" |
1 - #6 |
1.35" |
.050" |
1.45" |
1400 |
|
| CW08575 |
1 |
4 |
.055" |
1 - #6 |
1.38" |
.050" |
1.48" |
1680 |
|
| CW08576 |
1/0 |
4 |
.055" |
1 - #6 |
1.55" |
.050" |
1.65" |
2040 |
|
| CW08577 |
2/0 |
4 |
.055" |
1 - #6 |
1.60" |
.060" |
1.72" |
2420 |
|
| CW08578 |
3/0 |
4 |
.055" |
1 - #4 |
1.74" |
.060" |
1.86" |
3000 |
|
| CW08579 |
4/0 |
4 |
.055" |
1 - #4 |
1.95" |
.060" |
2.07" |
3650 |
|
| CW08580 |
250MCM |
4 |
.065" |
1 - #4 |
2.05" |
.060" |
2.17" |
4190 |
|
| CW08581 |
350MCM |
4 |
.065" |
1 - #3 |
2.46" |
.075" |
2.61" |
5820 |
|
| CW08582 |
500MCM |
4 |
.065" |
1 - #2 |
2.78" |
.075" |
2.90" |
8100 |
|
| CW08583 |
750MCM |
4 |
.080" |
1 - #1 |
3.38" |
.085" |
3.55" |
12060 |
|
| Displaying 1 to 13 (of 13 products) |
Result Pages: 1 |
| Application |
| Suitable for power, lighting, control, and signal circuits in a variety of industrial locations including pulp and paper, chemical, and petrochemical.
|
| Continuous corrugated armor provides excellent mechanical resistance and can be used as an electrical shield when adequate grounding is maintained.
|
| Per NEC Art. 300, may be used
|
| 1) indoors or outdoors,
|
| 2) in raceway or cable tray,
|
| 3) as aerial cable cable on a messenger,
|
| 4) in direct burial applications, and
|
| 5) in hazardous locations per NEC Class I, II, and III, Divisions 1 and 2.
|
| Standards |
| UL Standard 1569 for Type MC Cables.
|
| Passes UL & IEEE 70,000BTU Flame Test.
|
| UL Standard 44 for XHHW-2 conductors.
|
| ICEA S-95-658/NEMA WC70 for Nonshielded 0 - 2KV Cables. (Formerly ICEA S-66-524/NEMA WC7).
|
| NEC Article 330 for Metal Clad Uses and Constructions.
|
| UL Standard 2225 for Metal Clad Cables in Hazardous Locations.
|
|
|