CONTINUOUS CURRUGATED ARMOR CABLE
3 CONDUCTOR W/GROUND 15KV SHIELDED
EPR INSULATION, 133% INSULATION LEVEL
UL TYPE MC-HL, MV-105, CT USE
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
CLASS B STRANDED BARE COPPER.
|
| INSULATION: |
EXTRUDED NONMETALLIC SEMI-CONDUCTING LAYER.
|
| INSULATION: |
THERMOSETTING ETHYLENE PROPYLENE RUBBER (EPR).
|
| INSULATION SHIELDING: |
|
| NONMETALLIC LAYER: |
SEMI-CONDUCTING LAYER DIRECTLY OVER INSULATION.
|
| METALLIC LAYER: |
LAPPED COPPER TAPE DIRECTLY OVER NONMETALLIC LAYER.
|
| CONDUCTOR IDENTIFICATION: |
PHASE CODED WITH SUITABLE MARKING ON EACH CONDUCTOR.
|
| CONDUCTOR ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND IN ONE OF THE INTERSTICES, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE.
|
| ARMOR: |
CONTINUOUS CORRUGATED ALUMINUM.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT RED PVC APPLIED OVER ARMOR.
|
| Charlotte Wire Part# ↑ |
Size AWG |
Insulation Thickness (in.) |
Ground Size (AWG) |
Armor Diameter (in.) |
PVC Jkt Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Amps* |
Add to Quote Cart |
| CW08741 |
1000MCM |
.220" |
1-1/0 |
4.52" |
.085" |
4.69" |
15140 |
860 |
|
| CW08740 |
750MCM |
.220" |
1-1/0 |
3.92" |
.085" |
4.09" |
11640 |
745 |
|
| CW08739 |
500MCM |
.220" |
1-#1 |
3.55" |
.085" |
3.72" |
8550 |
600 |
|
| CW08738 |
350MCM |
.220" |
1-#2 |
3.23" |
.075" |
3.38" |
6620 |
490 |
|
| CW08737 |
250MCM |
.220" |
1-#3 |
2.89" |
.075" |
3.04" |
5280 |
400 |
|
| CW08736 |
4/0 |
.220" |
1-#3 |
2.76" |
.075" |
2.91" |
4710 |
360 |
|
| CW08735 |
3/0 |
.220" |
1-#3 |
2.65" |
.075" |
2.80" |
3850 |
315 |
|
| CW08734 |
2/0 |
.220" |
1-#4 |
2.54" |
.075" |
2.69" |
3590 |
275 |
|
| CW08733 |
1/0 |
.220" |
1-#4 |
2.46" |
.075" |
2.61" |
3160 |
240 |
|
| CW08732 |
1 |
.220" |
1-#4 |
2.32" |
.060" |
2.44" |
2800 |
210 |
|
| CW08731 |
2 |
.220" |
1-#6 |
2.30" |
.060" |
2.42" |
2580 |
185 |
|
| Displaying 1 to 11 (of 11 products) |
Result Pages: 1 |
| *Ampacity based on 3 conductor isolated in air with 105°C conductor temperature and 40°C ambient temperature per 2005 NEC Table 310.71
|
| Application |
| Suitable for power circuits rated up to 15000Volts 133% Insulation Level (ungrounded) in industrial, commercial, and utility locations. Per NEC Article 330, may be used 1)indoors or outdoors, 2)raceways and cable tray systems including ladders, troughs, and channels, 3)aerial cable on a messenger, and 4)in hazardous locations per NEC Class 1 Division 2, Class II Division 2, and Class III Division 1 and 2.
|
| Standards |
| Passes UL & IEEE 70,000BTU Flame Test.
|
| ICEA S-93-639/NEMA WC74 for Shielded Power Cables.
|
| (Formerly ICEA S-68-516/NEMA WC-8).
|
| UL 1072 for Medium Voltage Cables.
|
| NEC Article 330 for Metal Clad Cable.
|
| NEC Article 392 for Tray Use.
|
|