CONTINUOUS CURRUGATED ARMOR CABLE
3 CONDUCTOR W/GROUND 15KV SHIELDED
EPR INSULATION, 133% INSULATION LEVEL
UL TYPE MC-HL, MV-105, CT USE

Construction:
CONDUCTOR: CLASS B STRANDED BARE COPPER.
INSULATION: EXTRUDED NONMETALLIC SEMI-CONDUCTING LAYER.
INSULATION: THERMOSETTING ETHYLENE PROPYLENE RUBBER (EPR).
INSULATION SHIELDING:
NONMETALLIC LAYER: SEMI-CONDUCTING LAYER DIRECTLY OVER INSULATION.
METALLIC LAYER: LAPPED COPPER TAPE DIRECTLY OVER NONMETALLIC LAYER.
CONDUCTOR IDENTIFICATION: PHASE CODED WITH SUITABLE MARKING ON EACH CONDUCTOR.
CONDUCTOR ASSEMBLY: CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND IN ONE OF THE INTERSTICES, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE.
ARMOR: CONTINUOUS CORRUGATED ALUMINUM.
OVERALL JACKET: SUNLIGHT RESISTANT, FLAME RETARDANT RED PVC APPLIED OVER ARMOR.
 Charlotte Wire Part# ↓   Size AWG   Insulation Thickness (in.)   Ground Size (AWG)   Armor Diameter (in.)   PVC Jkt Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Amps*   Add to Quote Cart 
CW08731 2 .220" 1-#6 2.30" .060" 2.42" 2580 185 Request Quote For This Product 
CW08732 1 .220" 1-#4 2.32" .060" 2.44" 2800 210 Request Quote For This Product 
CW08733 1/0 .220" 1-#4 2.46" .075" 2.61" 3160 240 Request Quote For This Product 
CW08734 2/0 .220" 1-#4 2.54" .075" 2.69" 3590 275 Request Quote For This Product 
CW08735 3/0 .220" 1-#3 2.65" .075" 2.80" 3850 315 Request Quote For This Product 
CW08736 4/0 .220" 1-#3 2.76" .075" 2.91" 4710 360 Request Quote For This Product 
CW08737 250MCM .220" 1-#3 2.89" .075" 3.04" 5280 400 Request Quote For This Product 
CW08738 350MCM .220" 1-#2 3.23" .075" 3.38" 6620 490 Request Quote For This Product 
CW08739 500MCM .220" 1-#1 3.55" .085" 3.72" 8550 600 Request Quote For This Product 
CW08740 750MCM .220" 1-1/0 3.92" .085" 4.09" 11640 745 Request Quote For This Product 
CW08741 1000MCM .220" 1-1/0 4.52" .085" 4.69" 15140 860 Request Quote For This Product 
Displaying 1 to 11 (of 11 products) Result Pages:  1 
*Ampacity based on 3 conductor isolated in air with 105°C conductor temperature and 40°C ambient temperature per 2005 NEC Table 310.71
Application
Suitable for power circuits rated up to 15000Volts 133% Insulation Level (ungrounded) in industrial, commercial, and utility locations. Per NEC Article 330, may be used 1)indoors or outdoors, 2)raceways and cable tray systems including ladders, troughs, and channels, 3)aerial cable on a messenger, and 4)in hazardous locations per NEC Class 1 Division 2, Class II Division 2, and Class III Division 1 and 2.
Standards
Passes UL & IEEE 70,000BTU Flame Test.
ICEA S-93-639/NEMA WC74 for Shielded Power Cables.
(Formerly ICEA S-68-516/NEMA WC-8).
UL 1072 for Medium Voltage Cables.
NEC Article 330 for Metal Clad Cable.
NEC Article 392 for Tray Use.