CONTINUOUS CORRUGATED ARMOR CABLE
3 CONDUCTORS W/GROUND 2400VOLT NONSHIELDED
EPR INSULATION, 90°C
UL TYPE MC, MV-90, CT USE

Construction:
CONDUCTOR: CLASS B STRANDED BARE COPPER.
STRAND SHIELD: EXTRUDED NONMETALLIC SEMI-CONDUCTING LAYER.
INSULATION: THERMOSETTING ETHYLENE PROPYLENE RUBBER (EPR).
CONDUCTOR IDENTIFICATION: PHASE CODED WITH SUITABLE MARKING ON EACH CONDUCTOR.
CONDUCTOR ASSEMBLY: CONDUCTORS ARE CABLED TOGETHER WITH STRANDED COPPER GROUND IN ONE OF THE INTERSTICES, SUITABLE FILLERS WHERE NECESSARY, AND OVERALL CABLE BINDER TAPE.
ARMOR: CONTINUOUS CORRUGATED ALUMINUM ARMOR.
OVERALL JACKET: SUNLIGHT RESISTANT, FLAME RETARDANT YELLOW PVC APPLIED OVER ARMOR.
 Charlotte Wire Part# ↑   Size AWG   Insulation Thickness (in.)   Ground Size (AWG)   Armor Diameter (in.)   PVC Jkt Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Amps*   Add to Quote Cart 
CW08684 1000MCM .115" 1 - 1/0 3.30" .085" 3.47" 13000 590 Request Quote For This Product 
CW08683 750MCM .115" 1 - 1/0 3.00" .075" 3.15" 9880 525 Request Quote For This Product 
CW08682 500MCM .115" 1 - #1 2.60" .075" 2.75" 6850 425 Request Quote For This Product 
CW08681 350MCM .115" 1 - #2 2.32" .075" 2.47" 5120 350 Request Quote For This Product 
CW08680 250MCM .115" 1 - #3 2.06" .060" 2.18" 3870 280 Request Quote For This Product 
CW08679 4/0 .115" 1 - #3 1.97" .060" 2.09" 3410 255 Request Quote For This Product 
CW08678 3/0 .115" 1 - #3 1.81" .060" 1.93" 2960 220 Request Quote For This Product 
CW08677 2/0 .115" 1 - #4 1.74" .060" 1.86" 2400 190 Request Quote For This Product 
CW08676 1/0 .115" 1 - #4 1.60" .060" 1.72" 2040 165 Request Quote For This Product 
CW08675 1 .115" 1 - #4 1.49" .050" 1.59" 1760 140 Request Quote For This Product 
CW08674 2 .115" 1 - #6 1.44" .050" 1.54" 1440 125 Request Quote For This Product 
CW08673 4 .115" 1 - #6 1.30" .050" 1.40" 1120 91 Request Quote For This Product 
CW08672 6 .115" 1 - #6 1.20" .050" 1.30" 895 69 Request Quote For This Product 
CW08671 8 .115" 1 - #8 1.06" .050" 1.16" 650 52 Request Quote For This Product 
Displaying 1 to 14 (of 14 products) Result Pages:  1 
*Ampacity based on 3 conductor in isolated conduit in air with 90°C conductor temperature and 40°C ambient temperature per 2005 NEC Table 310.75.
Application
Suitable for power circuits rated up to 2400Volts in industrial, commercial, and utility locations.
Per NEC Art. 330, may be used
1) indoors or outdoors,
2) in raceways and cable tray systems including ladders, troughs, and channels,
3) as aerial cable cable on a messenger,
4) in hazardous locations per NEC Class I, II, and III, Divisions 1 and 2.
Standards
UL Standard 1569 for Type MC Cables.
Passes UL & IEEE 70,000BTU Flame Test.
ICEA S-96-659/NEMA WC71 for Nonshielded 2001-5KV Cables.
(Formerly ICEA S068-516/NEMA WC 8).
UL 1072 for Medium Voltage Cables.
NEC Article 330 for Metal Clad Cables.